Centrifugal Fans Main Catalogue General notes 2019 Explanation of technical details Dynamic pressure Calculation of the dynamic pressure: Information p d2 = k d2 v 2 pfd2 Dynamic pressure at fan outlet in Pa kd2 Constant factor for calculation of the dynamic pressure ZAbluefin- qv Air flow in m3/h ECblue k-factors for calculation of the dynamic pressure Cpro-ECblue ZAbluefin Cpro/ZAcube C ZAvblue Vpro Size kd2 Size kd2 Size kd2 Size kd2 Size kd2 22C.1R 1.85 · 10-5 25I.CR 5.59 · 10-6 25C.CR 9.66 · 10-6 25C.1R 1.14 · 10-5 25V.VR 1.29 · 10-5 28I.CR 3.56 · 10-6 28C.CR 6.26 · 10-6 28C.1R 7.44 · 10-6 28V.VR 8.27 · 10-6 28V.1R 8,60 · 10-6 31I.CR 2.22 · 10 -6 31C.CR 4.01 · 10 -6 31C.1R 4.78 · 10 -6 31V.VR 5.12 · 10 -6 31V.1R 5.32 · 10-6 35I.CR 1.39 · 10-6 35C.CR 2.53 · 10-6 35C.1R 2.96 · 10-6 35V.VR 3.29 · 10-6 35V.1R 3.37 · 10-6 C-ECblue 40I.CR 8.62 · 10-7 40C.CR 1.61 · 10-6 40C.1R 1.82 · 10-6 40V.VR 1.87 · 10-6 40V.1R 2.13 · 10-6 45I.CR 5.39 · 10-7 45C.CR 1.00 · 10-6 45C.1R 1.13 · 10-6 45V.VR 1.22 · 10-6 45V.1R 1.36 · 10-6 50I.CR 3.54 · 10-7 50C.CR 6.22 · 10-7 50C.1R 7,14 · 10-7 50V.VR 8.12 · 10-7 50V.1R 8.82 · 10-7 56I.CR 2.25 · 10-7 56C.CR 4.06 · 10-7 56C.1R 4.65 · 10-7 56V.VR 5.27 · 10-7 56V.1R 5.37 · 10-7 63C.CR 2.58 · 10-7 63C.1R 2.98 · 10-7 63V.VR 3.45 · 10-7 63V.1R 3.36 · 10-7 ZAvblue 71C.1R 1.86 · 10-7 80C.1R 1.15 · 10-7 Vpro-ECblue Example: Cpro-ECblue Type RH45C-ZID.GG.CR, article no. 114613 ZAcube- Size Constant Housing fans RH25C.CR 60 RH28C.CR 75 RH31C.CR 95 RH35C.CR 121 RH40C.CR 154 components System RH45C.CR 197 pd2 = 197 · qv2 RH50C.CR 252 RH56C.CR 308 RH63C.CR 381 technology | Control | General notes ziehl-abegg.com 353 --- sivu 2 / page 2 --- General notes Centrifugal Fans Main Catalogue Aerodynamics and acoustics 2019 Aerodynamics and acoustics Measurement method fs in Pa as a funktion of the air flow rate qV1 in m3/h. Technical conditions of supply The specified performance data meet the respective requirements for accuracy AN2 for impellers without motor AN3 for fans with standard motors AN2 for impellers with ECblue motors (except EC055) AN3 for impellers with EC motor EC055 (see type key) AN4 for fans with AC external rotor motors in line with ISO 13348 and apply to the rated data and air per- formance curves at the rated voltage. The continuous line in the characteristic curve represents the optimum reliable operating range for fans. Fan test bench The fan characteristic curves are determined on a combined air performance and acoustic test bench. The fan characteristic curves are measured in compliance to DIN EN ISO 5801, respectively AMCA 210-99. The sound power levels are measured in compliance with DIN EN ISO 3745 and ISO 13347-3 using the enveloping surface measuring method. The figure below shows an example of the measuring setup. The fan intake is installed in the measuring chamber at free inlet and free exhaust (installation type A as per DIN EN ISO 5801 respec- tively AMCA 210-99). Air density The air temperature and humidity are conditioned during the measurement using heat exchangers and kept largely constant. The characteristic curves shown refer to the measuring density. The mean measuring density is 1.16 kg/m³. p p p p fs 354 ziehl-abegg.com --- sivu 3 / page 3 --- General notes Centrifugal Fans Main Catalogue Installation and usage information 2019 Installation and usage information Measuring device for determining air volume The active pressure process compares the static pressure before the inlet nozzle with the static pressure in the inlet nozzle at the place of greatest constriction (lowest free nozzle cross sectional area). Using the energy conservation principle, the active pressure (differential pressure of the static pressures) can be assigned to the air flow as follows: Under normal conditions at 20°C: Under fluctuating air conditions: qV . w qV= 20 · k20 · w Betr qv Air flow in m3/h w Differential pressure of the static pressures in Pa k Coefficient for specific nozzle properties, nozzle factor S Standard air density with 1.2 kg/m3 Air density at current operating point in kg/m3 L-KL-2995-2 | L-KL-2995-4 | Pw | Pw | Nozzle coefficients Size ZAbluefin Cpro C ZAvblue ZAvblue ZApilot Vpro with EC055 Standard k With guard Standard k With guard Standard k With guard Standard k Standard k Standard k Standard k grille kg grille kg grille kg 175 38 38 190 38 38 200 38 38 220 71 71 225 47 46 75 71 50 250 67 63 60 58 60 58 80 112 90 63 280 85 80 75 72 75 72 95 86 315 106 100 95 91 95 91 120 112 355 140 130 121 116 121 116 150 144 400 180 170 154 148 154 148 200 180 450 220 210 197 189 197 189 240 220 500 280 265 252 242 252 242 320 291 560 355 335 308 295 308 295 400 360 630 381 365 381 365 480 445 710 490 470 800 620 594 p = 1.20 kg/m³ Example: Notes pertaining to the measuring method If an active pressure of 700 Pa is measured for size GR63I, the air The measured values, which were determined using the active flow can be calculated as follows, using this simplified formula: pressure method, are subject to a tolerance of +/- 8.0% as they pertain to the airflow result. This tolerance is reached above a minimum air velocity of approx. 29.53 ft/s at the place of greatest constriction. qv w 3 /h The tolerances cannot be clearly quantified below this minimum air velocity. The corresponding active pressure / air flow characteristic curves can be downloaded from our website in the Download section under This air flow measuring method is only suitable for acceptance Product Information. measurements on site. For a more accurate air flow determination in the existing installa- The nozzle coefficients (k factors) were determined under labora- tion setup, a counter calibration of the air flow has to be carried out tory conditions and with an undisturbed supply. If inlet guard grilles on site to measure the active pressure. The nozzle factors deter- are used (fitted in front of the inlet nozzle), these nozzle factors mined during this process apply exclusively to this installation setup. cannot be used for air flow determination because of a change in the supply flow and other static pressures. 364 ziehl-abegg.com